UNIT 6 MCQ: Pressurisation

Search this section

Choose a question set and start learning or take an exam.

About this collection

CompEx questions are organised into topic-based sets including Ex d, Ex e, Ex n and intrinsic safety. Select a subject to study at your own pace or complete a timed practice attempt.

“CompEx — UNIT 6 MCQ: Pressurisation” contains 6 questions across 1 collection.

Learning

Learning mode has no timer. After answering, you see feedback and the correct options. You can return to a question and repeat a topic.

Exam

A practice exam lasts up to 60 minutes and includes up to 50 questions from the selected collection. Correct answers and results appear after completion.

Sample questions and answers

These examples come from the published collection. Choose Learning to study questions in sequence, or Exam to check your knowledge.

Levels of protection for pressurised enclosures are?

One correct answer

  • Ex p1, Ex p2& Ex p3
  • Ex px, Ex py& Ex pz✓ Correct answer
  • Ex pG& Ex pD
  • Ex pa, Ex pb or Ex pc
Where a pressurised enclosure contains no ignition source, which one of the following will suit an area requiring EPL Gb (Cat 2) equipment?

One correct answer

  • Ex py✓ Correct answer
  • No protection required
  • Ex px
  • Ex px or Ex pz
Which one of the following statements represents the type of protection Ex p:

One correct answer

  • The internal pressure has to be greater than 0.5 Bar
  • The air used for pressurisation shall be taken from a specified non-hazardous area✓ Correct answer
  • Pressurisation of the enclosure is intended to contain explosive gases
  • Switching on is only permitted after the enclosure has been pressurised for at least 15 minutes
The action required when loss of internal pressurisation occurs in an Ex p enclosure in an area requiring EPL Gc (Cat 3G) is:

One correct answer

  • Alarm sounds and all flameproof equipment must be isolated
  • On operation of alarm, automatic disconnection of all equipment
  • No action
  • On operation of alarm, immediate action taken to restore pressurisation✓ Correct answer
Where a pressurised enclosure contains no ignition source, which one of the following will suit an area requiring EPL Gc (Cat 3) equipment?

One correct answer

  • Ex py
  • No protection required✓ Correct answer
  • Ex px
  • Ex px or Ex pz

Before you start

Do I need to register to start?

Guest access lasts 23 minutes. Free registration lets you continue without limits, save progress and review mistakes in your account.

What language are the questions in?

Questions and answer options retain the language of the original bank. You can change the interface language separately.

Can I use my result as an official document?

No. This is independent practice. A result does not replace an examination, certificate or knowledge check by an authorised organisation.